ATS / PDU

The Tripp Lite profile and the ATS / PDU panel.

An ATS / PDU is an SNMP connection with the Tripp Lite ATS / PDU profile. The profile reads a Tripp Lite automatic transfer switch or switched PDU through its PowerAlert card: the source in use, the source availability, the transfer count, the main output, the general fault, each source's voltage, frequency and current, and the outlet states. This page covers what the profile reads and shows. The connection fields are on the source page.

Signals

<n> is the input or outlet number the device reports.

GroupAddressReports
Statussource#code, source.avail#code, source.transfers, load#code, fault#code, device.status#code, temp, state#code, rollup#codeThe source in use, which sources are available, the transfer count, the main output, the general fault, the device status, the temperature, the ATS state and the roll-up.
Inputinputs, input.nominal, input.<n>.voltage, input.<n>.frequency, input.<n>.currentThe input count and nominal voltage, and each input's voltage, frequency and current.
Outputoutput.voltage, output.current, output.power, output.powerfactor, output.ratingThe output voltage, current, power in watts, power factor and rating.
Outletsoutlets, outlets.on, outlet.<n>.state#code, outlet.<n>.name, outlet.<n>.current, outlet.<n>.powerThe outlet count, how many are on, and each outlet's state and name, with its current and power on a metered device.
Alarmsalarm#code, alarms.count, alarms.textThe alarm level, how many alarms are active, and their text.
Systemsystem.model, system.manufacturer, system.devicename, system.location, system.name, system.uptimeThe model, the manufacturer, the name and location set on the card, and the agent's name and uptime.

On connect, the connection creates a tag for each input and each outlet the device reports, up to 48 outlets. Every address, its OID sources and its codes are on the profiles page.

Alarm conditions

ConditionRaisesChecked by default
Transferred to source BON SOURCE BYes
Source lostNO SOURCE, SOURCE A LOST, SOURCE B LOSTYes
Fault / critical alarmGENERAL FAULT, or the critical alarm the card reportsYes
Output offOUTPUT OFFNo

An ATS that transfers between two good feeds by design can leave Transferred to source B unchecked and raise no alarm. What a checked condition does is on the Devices page.

Roll-up

The ATS state is a worst-of summary. It starts from the source in use, rises to ALARM while a checked condition is active, and reads NO DATA while the device answers nothing. The profile maps it onto the roll-up.

ATS stateRoll-up
NORMAL, on source ARUNNING
ON SOURCE BWARNING
ALARMALARM
OUTPUT OFFSTOPPED
NO DATANO DATA
OFFLINEOFFLINE

ATS / PDU panel

The family has one panel. It takes a connection under ATS / PDU connection and creates the managed tags it reads.

Detail levelShows
ChipThe name and the roll-up status.
CompactThe source, availability and output chips with an outlet strip and each source's voltage.
FullThe output row and an alarm row.

While the device does not answer, the panel shows a NO LINK chip with the time of the last good read and dims the last-known values.

Managed tags

The panel creates one managed tag per catalog address it reads, and the connection adds a tag for each input and outlet it finds. The tag library lists them under the connection with a pdu badge.

Every managed tag records history. While the overlay shows them, the DataBorder carries the source, the availability, the output, the fault, the state and the alarm tags, the output power, each input voltage and each outlet state. The other managed tags stay out of the DataBorder unless their Stream switch is on. See Tags.

Alarm context

With Alarm burst on, a checked condition that arrives sends its code and text and forces a full snapshot, so a clip that starts at the fault decodes on its own. See DataBorder.

Limitations

  • There is no figure for a power device.